130
· If the Run command is active at power up with 3-wire sequence wiring and 2-wire sequence setting (default),
the motor will run in reverse direction at power up. To avoid this, set b1-10 (Run Command at Power up)=0
(Ignore) to ignore an active Run command at power up.
3 : Local / Remote Selection
Switch the command source (Local/ Remote) by opening/ closing the terminal.
Terminal
Description
Open
Remote (If no terminal is assigned to E1-□□=4, b1-00 and b1-01 are enabled. If a
multi-function input terminal is assigned to E1-□□=4, this terminal determines the source
for frequency command and Run command.)
Closed
Local (Frequency command and Run command are entered from the keypad.
Note:
1. When a multi-function input terminal is assigned to Local/ Remote, the LO/RE key on the keypad is disabled.
2. LED indicator is lit in Local mode.
3. Local/ Remote cannot be switched during run. Refer to b1-05 for the run command action after switch.
4 : Command Source 1/2 Selection
Switches the command source by opening/ closing the terminal as per the following table.
Terminal
Description
Open
b1-00 (Frequency Command Selection 1) , b1-01 (Run Command Selection 1)
Closed
b1-07 (Frequency Command Selection 2) , b1-08 (Run Command Selection 2)
Note: This cannot be switched during run.
5 to 8 : Multi-Step Speed Command 1 to 4
Switches multi-step speed frequency commands L1-00 to L1-15. Refer to L1-00 to L1-15
(Frequency Command 1 to 16) for details.
9 : Jog Frequency
The Job frequency set by L1-16 is enabled when the terminal is closed. And the acceleration
and deceleration time will be the values set to C1-11 and C1-12.
10/ 11 : Up/Down Command
Allows the frequency command to be set to two external terminals. Always set E1-□□= 10 (Up
Command) and E1-□□= 11 (Down Command) in pair. To set the frequency by Up/ Down
command, set b1-00 or b1-07 (Frequency Command Selection) to 2 (Terminal Up/Down)
according to the following table.
Terminal
Drive Operation
Up Command (10)
Down Command ( 11)