141
2. In Closed-Loop Vector Control, the terminal closes when the motor speed is within the value set to P4-01.
Speed agree
OFF ON
Output
frequency or
motor speed
Frequency
command
P4-01
P4-01
Figure 6.55 Speed Agree Operation
3 : User-Defined Frequency (Speed ) Agree
When the output frequency and frequency command are both within the P4-00 (Frequency
Detection Level) level plus or minus the P4-01 (Frequency Detection Width) value, the output
terminal closes.
Terminal
Description
Open
Output frequency or frequency command is outside of the range of (P4-00 ± P4-01)
Closed
Output frequency and frequency command are both within the range of (P4-00 ±
P4-01)
Note:
1. The detection and the P4-00 level work in both forward and reverse directions.
2. Closed-Loop Vector Control為電機速度和頻率指令.
OFF
ON
Output
frequency
Frequency
command
ON ON ON
OFF OFF
P4-00
0 Hz
Frequency
command P4-01
Frequency
command
-P4-00 P4-01
Frequency + P4-01
-P4-00
-P4-00 + P4-01
During reverse
During
forward
P4-00 - P4-01
Frequency command - P4-01
P4-00 + P4-01
Frequency command + P4-01
Output
frequency
User-defined
speed agree
Figure 6.56 User-Defined Frequency (Speed ) Agree Operation
4 : Drive Ready