147
When a PID Feedback Low is detected, the assigned output terminal closes. When the PID
feedback value falls below the b5-12 level for longer than the time set to b5-13, the fault will
be detected. Refer to b5-11 on page 79
41 :PID Feedback High
When a PID Feedback High is detected, the assigned output terminal closes. When the PID
feedback value exceeds the b5-22 level for longer than the time set to b5-23, the fault will be
detected. Refer to b5-11 on page 79
42 : During KEB Operation
The assigned output terminal closes during KEB operation. Refer to KEB functionon page
187
43 : Retain
44 : During Fast Stop
The assigned output terminal closes during a fast stop. Refer to setting 21 and 22 (Fast Stop)
of multi-function Digital Inputs.
45 : Retain.
When the internal cooling fan alarm is triggered, the assigned output terminal closes.
46 Rotor Position Detection Complete
After the Run command is given and the rotor position detection is complete, the assigned
terminal closes.
47Retain
48Retain
49Brake Control
If E2-00 ~ E2-03 (Multi-Function Digital Output) is set to 49 (the brake control), when the run
command is ON and inverter output frequency P4-05 (mechanical brake release frequency),
the terminal is closed until the when the inverter operation command is OFF and the output
frequency P4-06 (mechanical brake operation frequency), the terminal is disconnected