153
A negative signal by the gain and voltage bias is limited to 0%.
3 : 0 to 5 V
A negative signal by the gain and voltage bias is limited to 0%.
E3-07 Terminal A2 Function Selection
Sets the function for terminal A2. Refer to Table 6.21 on page 166.
Terminal A2 Function Selection
E3-08/E3-09 Terminal A2 Input Gain / Voltage Bias
E3-08 sets the terminal A2 input gain as a percentage when inputting 10V. E3-09 sets the
terminal A2 input voltage bias as a percentage when inputting 0V.
E3-10 Terminal A2 (4-20mA disconnected selection)
Terminal A2 (4-20mA disconnected
selection)
0 : no disconnected selection
1 : By setting frequency P4-03,and displayed ANL
2 : Frequency is 0, and displayed ANL
3 : Stop immediately, and displayed the ACE
E3-11 Terminal A2 Input Filter Time
Terminal A2 Input Filter Time
Sets the terminal A2 primary delay filter time, which can stabilize the drive operation by
eliminating the interference. Long filter time stabilizes the drive but causes slow response to
the analog input signal changes.
E3-12 Analog Input Terminal Enable/ Disable Selection
Analog Input Terminal Enable/ Disable Selection
Enables the analog inputs when Multi-Function Terminal Input E1-□□ = 41 (Multi-Function