When the output current is higher than the P3-01 (Stall Prevention Level during Acceleration)
level for longer than the time set to P3-16, the drive decelerates using P3-11 (Stall
Deceleration Time during Acceleration). Refer to P3-11 for detais.
The drive reaccelerates when the output current drops 15% below the value set in P3-01.
Time
Time
Output
current
Output
frequency
P3-01
Deceleration using P3-11
15% ofP3-01
P3-16 Stall Prevention
Detection Time
P3-16 Stall Prevention
Detection Time
Figure 6.79 Stall Prevention during Acceleration for PM motors
P3-01 Stall Prevention Level during Acceleration
Sets the output current level to activate the Stall Prevention function during acceleration.
Stall Prevention Level during Acceleration
<1> The value is determined by A1-06 (ND/ HD Selection).
When the motor rating is smaller than the drive rating, using the default to run the motor
could cause motor to stall. If the stall occurs, set a smaller to this parameter.
Set P3-02 as well when running the motor in the constant power range.
P3-02 Stall Prevention Limit during Acceleration
when running the motor in the constant power range, the P3-01 value will be automatically
reduced.
Sets the lower limit of Stall Prevention in the constant power range as a percentage of the
drive rated output current.
Stall Prevention Limit during Acceleration