Output frequency
Time
Set deceleration time
Deceleration characteristics 
when Stall Prevention is 
triggered during deceleration
 
Figure 6.81 Stall Prevention during Deceleration Operation 
  P3-04  Stall Prevention Level during Deceleration  
Sets the voltage level to activate the Stall Prevention function during deceleration. 
Stall Prevention Level during Deceleration 
When the regenerative power boosts the main circuit DC voltage higher than the value set to 
this parameter during deceleration, the drive performs Stall Prevention during deceleration to 
prevent an oV (Overvoltage) fault. Lower this value if the load is too heavy which causes a rapid 
regenerative power increase.   
<1> This value is for a 200 V AC drive. Double this value for a 400 V AC drive.   
  P3-05  Stall Prevention during Run 
Stall Prevention during run prevents an oL1 (Motor Overload) fault when the motor is running 
at constant speed.   
 
Stall Prevention during Run 
Note:     
1.  Available  in  Open-Loop  V/F  Control,  Closed-Loop  V/F  Control  and  PM  Open-Loop  Vector  Control  control 
methods.   
2. Disable when the output frequency is below 6 Hz regardless the P3-05 and P3-06 settings.     
0 : Disabled 
The drive runs at the set frequency command. A heavy load might cause the motor too stall 
and triggered an oC (Overcurrent) or oL1 (Motor Overload) to stop the motor.   
1 : Enabled (Deceleration Time 1)