181 
 
P4-00 sets the detection level for the multi-function output terminal assigned to E2-□□  = 2 
(Frequency Agree), E2-□□=3 (User-Defined Frequency Agree), E2-□□=16 (Frequency Detection 
1) or    E2-□□=17 (Frequency Detection 2).   
P4-01 Sets the detection width for the multi-function output terminal.   
Frequency Detection Level 
Frequency Detection Width 
<1>  The  upper  limit  is  determined  by  the  values  set  to  d1-02  (Maximum  Output  Frequency),  d1-13  (Motor  2 
Maximum Output Frequency)and L2-00 (Frequency Command Upper Limit). 
 
  P4-02  Frequency Command Loss Detection Selection 
The  drive  can  detection  a  frequency  command  loss  from  terminal  A1  or  A2.  When  the 
frequency  command  falls  below  90%  of  the  command  within  the  time  set  in  P4-04,  the 
frequency command loss will be detected.   
 
100%
Analog frequency 
command
10%
Time
P4-04
ONOFF
Frequency 
command loss
( E2-00 to E2-03 
=9 )
 
Figure 6.83 Frequency Command Loss Detection Operation 
This  parameter  sets  the  drive  operation  when  a  frequency  command  loss  is  detected.  Set 
E2-00  to  E2-03  to  9  (Frequency  Command  Loss)  for  the  output  terminal  to  trigger  when 
frequency command loss occurs.   
Frequency Command Loss Detection Selection 
0 : Drive stop   
The drive runs according to the frequency command.     
1 : Continue operation according to the setting in P4-03.