183 
 
WARNING! Do not perform Fault Restart in applications such as lifting, which could cause the machine to drop the 
load.     
Fault Restart can be performed when the following faults occur.     
Overvoltage (Acceleration) 
Overvoltage (Deceleration) 
Overvoltage (Constant Speed) 
Overcurrent (Acceleration) 
Overcurrent (Deceleration) 
Overcurrent (Constant Speed) 
Set Fault Restart in P5-00 to P5-03.   
Set E2-00 to E2-03 to 14 (Fault Start) to output the signal to an external devices.   
  P5-00  Number of Auto Restart Attempts   
Sets the number of times to automatically attempt to restart the drive when detecting the fault 
listed above. The drive will stop operation when the restart attemps reach the number set in 
this parameter. Clear the cause of the fault manually and restart the drive.   
The number of auto restart attemps is reset to 0 in the following situations.   
·  The drive runs normally for 10 minutes after a fault restart.   
·  A fault is reset manually after the protection function is triggered.   
·  The power supply is cycled.   
Number of Auto Restart Attempts 
  P5- 01  Auto Restart Fault Output Operation 
Enables or disables the fault output via E2-□□= 11 (Fault) during Fault Restart. 
Auto Restart Fault Output Operation 
0 : Fault Output Disabled 
1 : Fault Output Enabled 
  P5-02  Fault Restart Interval Time 
Sets the amount of time between restart attempts.