1. The load is too heavy
2. The acceleration and
deceleration times are too
short
3. The voltage determined
by the V/F is too high
4. The drive capacity is too
small
5. The motor is driven
below the rated speed with
a high load
6. Torque compensation is
too high
7. Speed Search related
parameters are set
incorrectly
8. Power supply phase loss
causes output current
oscillation
1. Check loading capacity
» Reduce the load
2. Confirm acceleration and
deceleration times
»Increase C1-00 to C1-07
parameter settings
3. Adjust d1-02 to d1-11 settings
(V/F Characteristics)
Note: If d1-02 to d1-11 settings
are too low, load tolerance at low
speeds will be reduced
4. Use a larger drive
5. »Reduce the load at low speed
» Use a larger drive
» Set a lower value to C6-00
(Carrier Frequency)
6. Check the torque
compensation
» Set a lower value to C3-00
(Torque Compensation Gain)
until the current is decreased
and the motor does not stall.
7. Adjust parameters related to
Speed Search
» Adjust b3-01 (Speed Search
Operation Current)
8. Check the power supply for
phase loss