Chapter 7 P2P Service
7-7
If the desired port is selected, “P2P Channel Settings” window will appear for the user to define
P2P driver type applicable for the port.
[Fig. 7.3.4] P2P driver client setting
Drivers and details available in XGT FEnet I/F are as follows;
Items Details
P2P
Driver
User frame
definition
Used to send/receive data with user defined frame.
XGT client
XGT dedicated (Built-in) protocol
(The user doesn’t need to define the frame)
Modbus TCP
client
MODBUS TCP protocol of MDICON
TCP/UDP
Selects TCP or UDP. If user select Modbus TCP, this item is
fixed as TCP
Client/Server
Select Client/Server. If user select the protocol as
XGT/Modbus TCP, this item is fixed as Client
Partner Port
Inputs port number of partner. When defining protocol as
User frame definition,
user can define port number.
H400~H1024
For XGT client, this item is fixed as 2004 and Modbus TCP
client is fixed as 502.
Partner IP address Input IP address of Partner device
[Table 7.3.2] Type of P2P driver clients
Note
1) Partner IP address
In case XGT is client, set the IP address of server device, If server uses DHCP for dynamic IP
address, XGT can’t communicates with server because IP address changes. So server have to
use the fixed IP address.
If XGT or Modbus is selected as P2P driver type for the communication port, user defined frame
can not be registered.