Chapter 8 Dedicated Protocol Communication
8-17
Variable
Type
Device
function
Description
-
Bit
F00027
-
-
_BPRM_ER Bit F00028
Basic parameters
error
Displayed if basic parameters abnormal.
_IOPRM_ER Bit F00029
IO configuration
parameters error
Displayed if I/O configuration parameters
abnormal.
_SPPRM_ER Bit F0002A
Special module
parameters error
Displayed if special module parameter
abnormal.
_CPPRM_ER Bit F0002B
Communication module
parameters error
Displayed if communication module
parameter abnormal.
_PGM_ER
Bit
F0002C
Program error
Displayed if user program abnormal.
_CODE_ER Bit F0002D Program code error
Displayed if an indecipherable instruction
is met while uses program executed.
_SWDT_ER Bit F0002E
System watch-dog
error
Displayed if System watch-dog exceeded.
_BASE_POWER
_ER
Bit F0002F Power error Displayed if base power abnormal.
_WDT_ER Bit F00030 Scan watch-dog
Displayed if program scan time exceeds
scan watch-dog time specified with
parameters.
- -
F00031
F0003F
- -
5) _CNF_WAR
It displays all the warning flags related with continuation of the operation (DWORD, F004~F005)
Variable
Type
Device
Function
Description
_RTC_ER
Bit
F00040
RTC data error
Displayed if RTC data abnormal.
_DBCK_ER Bit F00041 Data back-up error
Displays that n
ormal (hot or) warm restart
program unavailable
due to damaged data
memory, thus clod-restart executed,
which will
be available in initialization program
. If the
initialization program complete
, it will be reset
automatically.
_HBCK_ER
Bit
F00042
Hot restart unavailable
-
_ABSD_ER Bit F00043 Abnormal operation stopped
Displays that continuous operation not
allowed with the synchronized data kept in
scan unit when program stopped in the middle
due to power-cut while program executed
and
then powered back, which is available in
initialization program. If the initialization
program complete, it will be reset
automatically.