Chapter 5 XG5000 Program
5-12
Classification
Description
Subnet mask
Value necessary to check if destination station is on the same network of the
applicable station.
Gateway
IP address of Gateway or Router to transmit/receive data through the public network
or a network different from the network where the applic
able FEnet module is
included.
DNS server
Specify the IP address of domain name server.
DHCP
Check DHCP option when not fixed but dynamic IP is to be used (ADSL).
Relay
Using when send frame received at one port to another port.
Reception
wating time
If there is no request during the specified time from the host PC or MMI connected for
dedicated communication,
it will end the dedicated service connection regardless of
normal ending procedures supposing that the higher level system is with error. This
time is used in dedicated service to reset the channel
when any error occurs on the
destination station or the cable is disconnected.
Number of
dedicated
connections
Max. number of TCP dedicated services accessible at a time. (1~16)
A->B, B->A
This option
is activated When One IP Solution is not is not used. After setting
parameter of A side or B side, if you click A->B, B->A, the parameters
in one side is
copied into another side.
2) Driver (server) setting
Classification
Description
XGT server
Set when operated as dedicated communication server (slave)
Modbus TCP/IP server
Set when operated as Modbus server driver (slave)
3) Host table setting
Classification
Description
Enable host table
Access allowed to applicable module of IP address registered in host table
(unregistered client(IP address) is prohibited from connection when enabled)
Notes
(Note 1) Notice in setting DHCP
(1) To check the IP address after DHCP setting, check IP address in Online -> System diagnosis ->
Detailed module information or click standard setting after executing Open From PLC.
(2) In case of flexible IP address, IP address is reset when module is disconnected from server or Power is
off
(3) In case of using Remote connection to module using DHCP, when remote side restar
t, you have to
check the IP address of remote station
(4) In case of using DHCP with XGL-EFMTB/EFMFB, you have to use only port 1.