3  Selection of inverter module
Forming of the DC-link capacitors
To form the DC-link capacitors the inverter modules must be connected to
the mains power at 400/460 V  (CDA34.xxx) approx. every 6 months for
1 hour. The time is dependent on the storage temperature: Inverter
modules stored at approx. 45 °C only need be connected to the mains
approx. every 8 months. 
Figure 3.4 Inverter module rating plate with year and month identification
Attention: If the inverters have been left standing for more than 
8 months after shipping (see rating plate) the DC-link 
capacitors must be reformed. This can be avoided if the 
inverters are connected to the mains for one hour 
approx. every 6 months.
Of course you can also arrange for our Service department to carry out
the forming.
LUST Service Center Tel. 06441 / 966-136