3-6
Engineering Guide CDA3000
3 Selection of inverter module
3.1.2 Ambient
conditions
EN 50081-1 Residential and business
Motor cable length - See
section 6.4
Protection against emission of electri-
cal, magnetic and electromagnetic
interference and against conducted
interference
EN 50081-2 Industrial
Motor cable length - See
section 6.4.2
Protection against emission of electri-
cal, magnetic and electromagnetic
interference and against line-borne
interference
EN 55011 Industrial
Class A
Protection against line-borne interfer-
ence
Residential and business
Class B
Motor cable length - See
section 6.4
Standard Test Comments
Table 3.4 Explanation of the “Acceptance tests and standards” table
Feature Characteristic data
Tempera-
ture range
in operation
-10 ... 45 °C with derating to 55 °C (BG1 ... BG5)
0 ... 40 °C (BG6 ... BG8)
in storage -25 ... +55 °C
in transit -25 ... +70 °C
Relative air humidity 15 ... 85 %, condensation not permitted
Mechanical
strength to
IEC 68-2-6
in stationary
operation
Vibration: 0.075 mm in frequency range 10 ... 58 Hz
Shock: 9.8 m/s
2
in frequency range >58 ... 500 Hz
in transit Vibration: 3.5 mm in frequency range 5 ... 9 Hz
Shock: 9.8 m/s
2
in frequency range >9 ... 500 Hz
Protection Device menu IP20 (NEMA 1)
Cooling
method
Cold plate IP20
Push-through heat sink IP54 (3...15kW)
Push-through heat sink IP20 (22...37kW)
Touch protection VBG 4
Power reduction See section 3.2.x
Table 3.5 Ambient conditions