Engineering Guide CDA3000
3-7
3 Selection of inverter module
DE
EN
1
2
3
4
5
6
7
A
3.1.3 Installation
and cooling
methods
The CDA3000 inverter module offers three different methods of installa-
tion and cooling:
Cold plate
Wall mounting with heat sink
Push-through heat sink
General project planning notes
Subject Project planning notes
Side clearance
Inverter modules 0.37 to 15 kW can be mounted next to each
other with no gap.
Above 22 kW a side clearance of 50 mm must additionally be
maintained.
Clearance above
and below
There must be a clearance of 100 mm above and below.
Polluted cooling air (dust, fluff, oil, aggressive gases) may impair
the functioning of the inverter modules.
- Take adequate precautions; cold plate; separate
ventilation; installation of filters; regular cleaning etc.
Do not exceed the permissible range of the operational cooling
temperature (see sections 3.1.2 and 3.2.14).
Observe other ambient conditions (see section 3.1.2).
Mounting orientation: Vertical on the rear of the switch cabinet or
other mounting surface.
With “cold plate and push-through heat sink” cooling, comply
with the special conditions for discharge of power loss.
Table 3.6 Project planning notes