EasyManua.ls Logo

Lust CDA3000 - Power Reduction

Lust CDA3000
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Engineering Guide CDA3000
3-33
3 Selection of inverter module
DE
EN
1
2
3
4
5
6
7
A
3.2.14Power
reduction
The maximum permissible inverter rated current and the peak current are
specified referred to 400 V mains voltage, a 10/25 m motor cable, a power
stage clock frequency of 4 kHz and an ambient temperature of 45 °C.
If background conditions such as the mains voltage, motor cable length,
power stage clock frequency or ambient temperature change, the max.
permissible current load on the inverter modules also changes. For
details of which current load on the power stage modules is permissible
under which changed background conditions, refer to the following char-
acteristic diagrams and tables.
Maximum output current as a function of mounting height
Figure 3.7 Current correction factor (KH) as a function of mounting height
0
1000
2000
3000 4000
0.6
0.7
0.8
0.9
1.0
H [m]
K
1% per 100 m
H
~
~

Table of Contents

Other manuals for Lust CDA3000

Related product manuals