3-34
Engineering Guide CDA3000
3  Selection of inverter module
Permissible rated current of the single-phase inverter modules 
0.37 kW to 2.2 kW
1 x 230 V mains voltage
45 °C ambient temperature
4 kHz clock frequency
10 m motor cable
40 °C ambient temperature
8 kHz clock frequency
10 m motor cable
40 °C ambient temperature
16 kHz clock frequency
10 m motor cable
45 °C ambient temperature
4 kHz clock frequency
25 m motor cable
40 °C ambient temperature
8 kHz clock frequency
25 m motor cable
40 °C ambient temperature
16 kHz clock frequency
25 m motor cable
Inverter modules
Rated current
[A] 
Rated current
[A] 
Rated current
[A] 
Rated current
4)
[A] 
Rated current
4)
[A] 
Rated current
4)
[A] 
CDA32.003,Cx.x
1 )
2.40 2.40 2.40 2.25 2.15 2.00
CDA32.004,Cx.x
2 )
4.00 4.00 3.00 3.85 3.70 2.60
CDA32.006,Cx.x
5.60 5.40 4.00 5.45 5.25 3.85
CDA32.008,Cx.x
3 )
7.10 7.10 5.20 6.95 6.85 4.80
1) Mounted side-by-side, with no additional cooling area
2) Mounted side-by-side, with backplane (940 mm x 70 mm = 0.065 m²) as additional cooling area
3) inverter module With Heat sink “HS32.200” 
4) The rated current with a 25 m motor cable is less than that with a 10 m motor cable by the amount of the current loss occurring on the motor 
cable (see table 3.2.7)
Table 3.24 Output current for inverter modules with 230 V power supply