Engineering Guide CDA3000
3-35
3  Selection of inverter module
DE
EN
1
2
3
4
5
6
7
A
Permissible rated current of three-phase inverter modules 
0.75 kW to 90 kW
3 x 400 V mains voltage
45 °C ambient temperature
4 kHz clock frequency
10 m motor cable
40 °C ambient temperature
8 kHz clock frequency
10 m motor cable
40 °C ambient temperature
16 kHz clock frequency
10 m motor cable
45 °C ambient temperature
4 kHz clock frequency
25 m motor cable
40 °C ambient temperature
8 kHz clock frequency
25 m motor cable
40 °C ambient temperature
16 kHz clock frequency
25 m motor cable
Inverter modules
Rated current
[A] 
Rated current
[A] 
Rated current
[A] 
Rated current
[A] 
Rated current
[A] 
Rated current
[A] 
CDA34.003,Cx.x
1 )
2.2 2.2 1.4 2.0 1.7 0.5
CDA34.005,Cx.x
2 )
4.1 4.2 2.3 3.9 3.6 1.4
CDA34.006,Wx.x
5.7 5.7 3.5 5.7 5.7 2.6
CDA34.008,Wx.x
7.8 7.8 * 7.8 * *
CDA34.010,Wx.x
10 10 * 10 * *
CDA34.014,Wx.x
14 14 * 14 * *
CDA34.017,Wx.x
17 17 * 17 * *
CDA34.024,Wx.x
24 24 * 24 * *
CDA34.032,Wx.x
32 32 * 32 * *
CDA34.045,Wx.x
45 45 * 45 * *
CDA34.060,Wx.x
60 60 * 60 * *
CDA34.072,Wx.x
72 72 * 72 * *
CDA34.090,Wx.x
90 90 * 90 * *
CDA34.110,Wx.x
110 110 * 110 * *
CDA34.143,Wx.x
143 143 * 143 * *
CDA34.170,Wx.x
170 170 * 170 * *
*  Not available at time of going to press
1) Mounted side-by-side, with no additional cooling area
2) Mounted side-by-side with heat sink “HS32.200” or with 0.3 m² backplane
Table 3.25 Output current for inverter modules with 400 V power supply