Engineering Guide CDA3000
6-15
6 Selection of supplementary components
DE
EN
1
2
3
4
5
6
7
A
6.4.2 Permissible
motor cable
length with
internal RFI filter
[A] [B] [C] [D] [E] [F]
4 kHz power stage clock
frequency
8 kHz 8 kHz power stage contact
frequency
16 kHz power stage contact
frequency
Inverter
module
Rec. 4-pole
standard
motor
[kW]
With integral
mains filter
With [A] and
line choke U
K
=4%
With integral
mains filter
With [C] and
line choke U
K
=4%
With integral
mains filter
With [E] and line
choke U
K
=4%
Class
A
[m]
1)
Class
B
[m]
1)
Class
A
[m]
1)
Class
B
[m]
1)
Class
A
[m]
1)
Class
B
[m]
1)
Class
A
[m]
1)
Class
B
[m]
1)
Class
A
[m]
1)
Class
B
[m]
1)
Class
A
[m]
1)
Class
B
[m]
1)
CDA32.003 0.375 kW 25 10 25 10 25 10 25 10 25 - 25 -
CDA32.004 0.75 kW
25 10 25 10 25 10 25 10 25 - 25 -
CDA32.006 1.1 kW
15 10 15 10 25 15 25 15 25 - 25 -
CDA32.008 1.5 kW
15 15 15 15 25 15 25 15 25 - 25 -
CDA34.003 0.75 kW
15 15 25 15 25 10 25 15 25 - 25 -
CDA34.004 1.1 kW
15 15 25 15 25 10 25 15 25 - 25 -
CDA34.005 1.5 kW
15 15 25 15 25 10 25 15 25 - 25 -
CDA34.006 2.2 kW
15 15 25 15 25 10 25 10 25 - 25 -
CDA34.008 3.0 kW
25 10 25 15 25 - 25 10 25 - 25 -
CDA34.010 4.0 kW
25 10 25 15 25 - 25 10 25 - 25 -
CDA34.014 5.5 kW
25 10 25 15 25 10 25 25 15 - 25 15
CDA34.017 7.5 kW
25 10 25 15 25 10 25 25 15 - 25 15
1) Maximum permissible motor cable length at which the standard is maintained
Table 6.14 Permissible motor cable length with integral mains filter
dependent on standard EN 55011 A/B