Engineering Guide CDA3000
4  Software functions
5. Start automatic motor identification
5.1 Call up parameter ENSC and set to “START”.
The motor identification takes approx. 3-4 minutes. When the 
identification is complete parameter ENSC is automatically reset 
to “STOP”.
6. Selection of control mode
6.1 Call up parameter CFCON and set to “SFC”.
The “Sensorless Flux Control” mode for optimum dynamics with-
out speed feedback is activated.
7. Save all parameters to one of the four user data sets.
7.1 Call up parameter UMWR and enter the value “1” for user data 
set 1.
Note: Only by saving the data sets to one of the user data sets are 
the data from the volatile device RAM permanently stored. 
Otherwise changes to the active data set are lost on power-
off or in the event of an error reset.