4-18
Engineering Guide CDA3000
4 Software functions
ENPO X2-8 Power stage enable = High level
Switching level Low/High: <5 V / >12 V DC
•I
max
at 24 V = 10 mA
•R
IN
= 3 k
Delay
2µs
PLC-compatible (IEC1131)
Digital outputs
OSD00 X2-15 Short-circuit-proof
PLC-compatible (IEC1131)
•I
max
= 50 mA
Protection against inductive load
High-side driver
OSD01 X2-16 Short-circuit-proof with 24V supply from inverter
module
PLC-compatible (IEC1131)
•I
max
50mA
No internal freewheeling diode; provide external
protection
High-side driver
Data output with reference coupling
(restricted)
Relay output
OSD02 X2-18
X2-19
X2-20
Relay 48 V / 1 A AC, changeover contact
Usage category AC1
Operating delay approx. 10 ms
Motor temperature
PTC1/2 X3-1
X3-2
Measured voltage max. 12 V DC
Measuring range 100
- 15 k
suitable for PTC to DIN 44082
suitable for temperature sensor KTY84, yellow
Sampling time 5 ms
Voltage supply
+10.5V X2-1 Auxiliary voltage U
R
=10.5 V DC
Short-circuit-proof
•I
max
= 5 mA
+24V X2-6
X2-7
X2-13
Auxiliary voltage U
V
= 24 V DC
Short-circuit-proof
•I
max
= 200 mA (overall, also includes the driver
currents for outputs OSDox)
Des. Terminal Specification floating
MV = measured value
Table 4.5 Specification of control terminals