Engineering Guide CDA3000
5-7
5 Communication and user modules
DE
EN
1
2
3
4
5
6
7
A
Figure 5.5 Interconnection of Lust drive units on the CAN bus
1 Control
2 Connection of 24 V supply voltage
3 Bus termination plug with resistor 120
4 Lust system bus cable type I or self-defined cable
Cable type for self-assembly
If the supplied cables are not of the required length, it is also possible to
make your own cables (1:1 connection). This relates to LS-BUS cable
type I.
Voltage supply, CAN bus
Voltage 24 V +
20%
Voltage ripple 3 Vss
Current 100 mA per station
Table 5.4 Voltage supply
Cable type Shielded with at least nine wires
Wires
Twisted-pair, 0.25 mm
2
Surge impedance 120
Length Any, total distance must not exceed 80 mm
Table 5.5 Cable type
- +
24VDC
24 VDC
- - -
+
+
+
+
+
+
+
+
PLC
4
3
VF1000M VF1000M
VF1000S, G19
44
12345 16
17 18 19 20
11 12 13 14 15678910
12345 161718
19 20
11 12 13 14 15678910
12345
16 17 18 19 20
11 12 13
14 15
678910
CDA3000