Installation and Operation Manual
35
Refer to Table 6 for trouble event types and explanation of the events.
Table 6 Trouble Event Type
Category
Trouble Event Type
Explanation
System
PrimaryPower_Loss
Primary power is lost
Battery_Loss
Battery is disconnected
ControlPanel_Grounding
Control panel detects ground condition
PrimaryPower_OverVoltage
Primary power voltage is too high
Charger_OverVoltage
Charger voltage is too high
ArchiveFile_Missing
History record file is missing
ConfigFile_Missing
Configuration file is missing
ConfigFile_Damaged
Configuration file is damaged
Unit
ALU_Conf.Mismatch
ALU’s configuration file is mismatched with
AMI’s
AMI_Jumper
AMI jumper is in laptop access mode shorted
Unit_Missing
PCU/ALU/NOU/ROU/XNU is missing
Ext._Missing
The network annunciator is missing
Unit_Addr.Conflict
1. Two or more ALUs have the same
addresses, or
2. Two NOUs have the same addresses
Unit_ Illegal
The unit is working, but it is not configured
Unit_SwitchError
The unit address changed during running
Circuit
Ext._Illegal
The network annunciator is working, but it is
not configured
Ext._Grounding
The network circuit is grounded
Ext.__Addr.Conflict
Two or more annunciators on the network
circuit have the same address
Bus_Short
The Signaling Line Circuit is shorted
Bus_Open
The Signaling Line Circuit is open
Bus_CrossPower
The Signaling Line Circuit wire is cross power
NOU_CircuitTrbl
The notification appliance circuit is
malfunctioning (open, short, grounding, etc.)
Field Device
Heat_SensingError
The heat detector sensing has an error
Smoke_Contamination
The chamber of the smoke detector is