Agency Listings, Approvals
Underwriters Laboratories (UL/ULC)
Requirements for All Installations
The general requirements are described in this section. When installing an individual device, refer to the specific
section of the manual for additional requirements.
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code, CSA C22.1 Canadian
Electrical Code Part 1, CAN/ULC-S524, NBC, NBC, NFC, AHJ, and local code requirements.
2. Use the addressable smoke detectors listed in the compatibility chart (Appendix-A: Compatible Devices).
3. Use UL/ULC listed notification appliances compatible with the FW105 from those specified in Appendix-A:
Compatible Devices of this manual.
4. A full system verification must be performed every time the panel is programmed or reprogrammed.
Requirements for Local Protected Fire Alarm Systems
At least one UL listed supervised notification appliances must be used.