Installation and Operation Manual
54
Appendix-D: Battery Calculations
Total System Currents Calculations
Table 20 System Currents Calculation
IMPORTANT NOTICE
The main AC branch circuit connection for Fire Alarm Control Unit must provide a dedicated continuous
power without provision of any disconnect devices. Use #12 AWG wire with 600 volt insulation and proper
over-current circuit protection that complies with the local codes. For specifications, refer to the
Specifications and Features section.
Functional Unit's Currents (All currents are in ampere)
Model Number
Description
Qty
Standby
Total
Standby
Alarm
Total
Alarm
FW202
AMI
×
0.152
0.155
FW390
PSU
×
0.077
0.077
FW301
MFU
×
0.089
0.119
FW338
NOU
×
0.030
0.030
FW852
ISU
×
0.035
0.035
FW261A
LDU
×
0.028
0.105
Field Devices Currents (All currents are in ampere)
The total quantities of each loop must <= 252. The total current of field devices per loop is 100 mA @standby,
and 220 mA @alarm.
FW511
Optical Smoke Detector
×
0.00014
0.001
FW521
Heat Detector
×
0.0001
0.001
FFW721
Manual Station
×
0.0001
0.001
FW721C
Manual Station (Canada)
×
0.0001
0.001
FFW722
Manual Station
×
0.0001
0.001
FW722C
Manual Station (Canada)
×
0.0001
0.001
FW811
Input Module
×
0.00017
0.00079
FW811M
Mini Input Module
×
0.00017
0.0008
FW821
Input-Output Module
×
0.00015
0.00026
FW831
Relay Module
×
0.00015
0.00026
FW841
Conventional Zone Module
x
0.00015
0.0003
FW851
Isolator Module
×
0.0016
0.0108