Installation and Operation Manual
40
By-pass
The by-pass function is provided for user if they don’t want to receive message from specified devices.
Auto addressing
Auto addressing mode which is applied to assign addresses for field devices by panel. When panel goes
into Auto Addressing mode, devices installed on this loop will be automatically assigned addresses in
sequence which is convenient for field commissioning. Please refer to the programming manual for
details.
Event History
The control panel includes a non-volatile memory recording 5000 events, plus a separate 5000 alarm-only
events. Identified alarm, supervisory, trouble and other signal status, and other significant events will be
recorded along with the date and time of occurrence. These can be viewed by operating the front panel push
buttons.
To recall past events, proceed as follows:
Press the “MENU” button.
On the “MENU” display, select “Archive”
Press the “Enter” button.
Use the up button next to the LCD to see the previous event display.
Use the down button next to the LCD to see the next event display.
The history record rule is:
New events overwrite old events when filled.
The events are sorted by time occurrence sequence.
Events recorded in the history are:
Alarm, Supervisory, Trouble and Other Signal conditions
Alarm silence/Resound
System reset
System startup
Enable/disable function
Start and stop of Walk Test
Trouble/supervisory reminder
Trouble/supervisory restored to normal