EasyManua.ls Logo

Megger PAT4DV/3 - Test Mode Configuration; Manual;Autopass and Fail Buzzer Settings

Megger PAT4DV/3
51 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Setup Manual / Autopass Testing / Fail buzzer
If ‘AUTOPASS’ is selected, testing will proceed automatically with PAT4 determining the pass/fail status according to the pre-selected Group limits. If
‘MANUAL is selected, PAT4 will pause after each test and display a “Pass” / “Fail” decision prompt. The buzzer can be set to sound when a test fails
in AUTOPASS mode. To mute the buzzer following a failure, press the OK key.
1 From the Main screen, press the
MENU key.
2 From the Menu screen, press the
SETTINGS key.
3 Press the
MISC key.
4 Press the
TEST SETUP key. The current Manual / Autopass setting is shown.
5 Using the lower left key, toggle the Manual / Autopass setting as required.
6 To set up the Fail buzzer, press the
BUZZER key. Using either the OFF or ON key,
switch the buzzer feature off or on as required.
7 On completion use
ESCape to back up to the Menu screen (and Main screen if required).
TESTS QUICK-CHECK
COMMS MENU
ASSET
SETTINGS CLIENT
CLOCK
MISC USERS
TEST SETUP
COMPANY MEMORY
TEST TIMES
AUTOPASS BUZZER
Fail buzzer OFF
ON

Related product manuals