M
AVTMTTR310 Rev 8 May 2016
90
DATE (M/D/Y) : 06/01/1999 1:25
TEST: 003
TRANSFORMER ID: CHQ12-5899D
TYPE: THREE PHASE TRANSFORMER Dd6
TAPS TESTED: 3 - 16L
H VOLTAGE: 250000
X VOLTAGE: 50000
CALCULATED TURNS RATIO: 5.0000
TEST VOLTAGE: 80V
A B C
RATIO 5.006 4.998 5.011
% DEVIATION 0.12 -0.04 0.22
PHASE(min) 5.3 6.5 7.9
Iexc(ma) 8.5 9.1 7.6
Figure 6-15c. Sample Three-Phase Test Report