EasyManua.ls Logo

Megger TTR310 - Page 65

Megger TTR310
130 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SETUP AND CONNECTIONS
AVTMTTR310 Rev 8 May 2016
53
Table 5-5. CEI/IEC 76-1:2011 Transformer Winding Phase Relationship
Copyright 2009 Megger
Winding Connection Winding Tested
Diag
No.
IEC
Vector
Group
High-Voltage
Winding (U1)
Low-Voltage
Winding (U2)
Phase
Tested
Winding
Shorted
By TTR
High-
Voltage
Winding
Low-
Voltage
Winding
Measured
Turn Ratio
Remarks
27
Dzn10
U
V
W
1V-1W
1W-1U
1U-1V
1U-(1V+1W)
1V-(1W+1U)
1W-(1U+1V)
2N-2W
2N-2U
2N-2V
1.5U1
U2
Neutral
accessible
on zigzag
winding
28
Dz10
U
V
W
1U-1V
1V-1W
1W-1U
2U-2W
2V-2U
2W-2V
U1
U2
No neutral
accessible
on zigzag
winding
29
YNyn0
U
V
W
1U-1N
1V-1N
1W-1N
2U-2N
2V-2N
2W-2N
U1
U2
Neutral
accessible
on HV & LV
winding
30
YNy0
U
V
W
1V-1N
1W-1N
1U-1N
1U-1N
1V-1N
1W-1N
2U-2V
2V-2W
2W-2U
U1
U2
No neutral
accessible
on LV
winding
31
Yyn0
U+V
V+W
W+U
1U-1V
1V-1W
1W-1U
2U-2V
2V-2W
2W-2U
U1
U2
No neutral
accessible
on HV
winding
32
Yy0
U+V
V+W
W+U
1U-1V
1V-1W
1W-1U
2U-2V
2V-2W
2W-2U
U1
U2
No neutral
accessible
on HV & LV
windings

Table of Contents