EasyManua.ls Logo

Megmeet MV600 Series - Page 179

Default Icon
273 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
179
1: Frequency arrival signal (FAR)
Refer to the function description of P09.24.
2: Speed non-zero signal
When the drive is running, and the speed is higher than the P08.07 “stop speed”, the relevant indication
signal is output. The speed non-zero detection mode is set by P08.09 “stop speed detection mode”.
Note:
The zero speed detection is enabled in all the control modes.
3: Frequency level detection signal (FDT1)
Refer to the function description of P09.25~P09.26.
4: Frequency level detection signal (FDT2)
Refer to the function description of P09.27~P09.28.
5: Overload detection signal (OL)
When the drive output current exceeds the overload pre-alarm detection level, and the retention time
exceeds the overload pre-alarm detection time, the relevant indication signal will be output. It is usually
used for the overload pre-alarm. Refer to the description of P97.04~P97.05.
6: Lockout for under-voltage (LU)
When the DC bus voltage is lower than the under-voltage level, the relevant indication signal will be
output, and the LED displays “-LU-”.
7: External fault stop (EXT)
When the drive has external fault tripping alarm (Er.EFT), the relevant indication signal will be output.
8: Frequency upper limit (FHL)
When the set frequency frequency upper limit and the running frequency reaches the frequency upper
limit, the relevant indication signal will be output.
9: Frequency lower limit (FLL)
When the set frequency frequency lower limit and the running frequency reaches the frequency lower
limit, the relevant indication signal will be output.
10: Drive running at zero-speed
When the drive is running at zero speed, the relevant indication signal is output. To make it clear, in the
V/F mode, the indication signal is output when the output frequency is 0. In the non-V/F mode, the
indication signal is output when the feedback frequency is lower than the corresponding frequency of
P09.34.
11: Simple PLC stage running completion indication
When the current stage of simple PLC running is completed, the relevant indication signal will be output
(single pulse signal, width: 500ms).
12: PLC cycle completion indication
When the simple PLC completes an operation cycle, the relevant indication signal will be output (single
pulse signal, width: 500ms).
13: Reserved

Table of Contents

Related product manuals