Analog Input Modules
Isolated Input Module IOP301
Metso Automation MAX Controls Inc. 277596
2-3
The input circuit configuration for each type of input is shown in the
following sketch. An electronic fuse protects the 24-volt loop power to the
transmitter. A 200-Ohm thermistor in series with the 4-20 mA input provides
current limiting for voltages up to 100 Volts. The 24-volt loop supply is
available to the module from the backplane. For current inputs with external
shunt the channel is configured for voltage input and Rs = 0.