PL-565 Accumass BW500 Page 61
Parameters
P019 Manual Span Adjust
Provides a means for adjustment to the span calibration. (f=0)
The adjustment value is determined by performing material tests and is subsequently
entered either as a calculation of % change into P598, or as the weight of the
material test
entry:
1 = % change
2 = material test
Refer to Recalibration on page 41.
P022 Minimum Speed Frequency
Sets the minimum frequency that the speed sensor can reliably read. Signals at low
frequencies are erratic, adversely affecting the performance of the weighing system.
Entry:
1 = 1 Hz (at 1 Hz, it takes 1 s before defaulting to 0 speed)
2 = 2 Hz
f
(at 2 Hz, it takes 0.5 s before defaulting to 0 speed)
P080 Damping Display
P080-01 Rate
P080-02 Load
P080-03 Speed
Sets the speed of response to which the displayed readings (rate, load and speed),
and outputs (alarm and mA*) react to change.
Refer to Operation on page 89.
Note:
Effect of damping (P080-01) on mA output* can be overridden by mA output
damping (P220).
The higher the damping value, the slower the response.
Enter damping value, range 0.000
f
999
*Damping is not applicable to the mA output if programmed for PID function (P201 = 4).
P081 Display Scroll Mode
The run displays are scrolled either manually by pressing ALT DISP if the scroll mode
is set to off, or automatically if the mode is set to on.
entry:
0 = off
f
1 = on