Page 66 Accumass BW500 PL-565
Parameters
P212 mA Output Minimum
Sets the minimum mA limit for the output selected, outputs 1 to 3 (P212 - 01 to – 03).
The limit sets the lower mA range (0 or 4 mA) to a minimum output value. (f=3.80)
Enter limit value, range 0 - 22
P213 mA Output Maximum
Sets the maximum mA limit for the output selected, outputs 1 to 3 (P213 - 01 to – 03).
The limit sets the upper mA range (20 mA) to a maximum output value. (f=22.00)
Enter limit value, range 0 - 22
P214 4 mA Output Trim
Trims the 4 mA output level for the output selected, outputs 1 to 3 (P214 - 01 to –
03). The trim adjust the output to agree with a milliammeter or other external mA
input device.
Scroll the trim value up or down
P215 20 mA Output Trim
Trims the 20 mA output level for the output selected, outputs 1 to 3 (P215 - 01 to –
03). The trim adjust the output to agree with a milliammeter or other external mA
input device.
Scroll the trim value up or down
P220 mA Output Damping
Sets the damping for the output selected, outputs 1 to 3 (P220 - 01 to – 03). Damping
sets the speed at which the mA output reacts to change. The greater the damping
value, the slower the response. If the value is 0, the mA output assumes the damping
set in P080. (f=0.000)
Enter the damping value, range 0.001 – 999
P250 mA input range
Sets the mA range for the input selected, inputs 1 to 2 (P250 - 01 to – 02).
entry:
1 = 0 - 20 mA
2 = 4 - 20 mA
f