6. Operating | 6.2 - Configuration and adjustment via the keypad | 136
[Stop bits] StoP
Units for transmission protocols
Selection: 1, 2
Only with RS-485: [Mode] ModE
Selection: [Half duplex] HALF, full duplex FuLL
6. Press "Exit" to exit the setup menu.
7. Save the changes.
6.2.15 Entering fieldbus parameters using front-panel keys
1. Press and hold for 2–3 seconds.
SEtuP appears on the display.
2. Press "OK".
Cd 000 appears on the display (Cd flashes).
3. Press (12×) to select FP 080.
4. Press "OK".
FLd.Pro appears on the display.
5. Select the individual parameters and modify if required, see Chapters
Parameter table (setup) and Selecting parameters.
ProfiBus DP
[Fieldbus] PdP-U1
[PDP address] PdP.Adr
Input: 001…126
DeviceNet
[Fieldbus] dEV.nEt
[Baud rate] dVnbdr
Selection: 125, 250, 500
[Slave address] dVnAdr
Input: 001…062