9. Fieldbus interface | 9.2 - Scale protocol | 150
Field Size Function
CmdError 1 bit The device has interrupted the execution
of a command (e.g., standstill could not be
reached within the defined standstill time).
The error number can be read from "LASTER
ROR", see ChapterFunction number 4: adjust
ment information, error byte (read).
Tare_Active 1 bit The scale has been tared.
Cal_Changed 1 bit The device has been calibrated.
When this bit is 1, the weighing point para
meters (EXPO/UNIT/STEP+FSD) must be read
again.
Set after "Power on" and reset after reading
the FSD.
Test_Active 1 bit The device executes the ADC test. The read
weight value is not the gross value, but the test
value.
OutOfRange 1 bit Below zero or above Max (FSD).
Standstill 1 bit The scale is stable.
InsideZSR 1 bit The gross weight value is within the zero set
ting range.
CenterZero 1 bit The weight value is within center zero (0
±0.25d).
BelowZero 1 bit The weight value is negative (gross <0d).
Overload 1 bit The weight value has exceeded the measur
ing range. No valid weight data is specified
(gross>FSD+overload).
AboveMax 1 bit The weight value has exceeded Max (FSD),
but is still within Max + permissible overload
(gross≤FSD+overload).
ADCError 1 bit AD conversion error, see ChapterFunction
number 1: scale status (read).