MIRCOM TECHNOLOGIES LIMITED, 9500 Series: No Subscriber Line Page 35
Press * to abort or # to store entry. To quit, enter *000 while at the PROGRAM MODE menu to return to NORMAL
MODE.
ELEVATOR-RECALL RESTRICTION (9502A ONLY)
The system can provide elevator-recall (restriction). Scroll down to the following feature.
[1=Bck] [3=Fwd]
Do you want to edit
Elevator-Recall ID?
[*=Abort] [#=Yes]
Press # to edit. The menu should appear ...
-Program Options-
Elevator-Relay
Card 1-8, 9-0 0
Please enter choice:
Enter one digit 1 to 8 for Elevator Restriction feature. Enter 0 or 9 for normal operation without elevator-recall
(restriction). For more information see the Elevator-Recall (Restriction) section in this manual.
SET ON-LINE TIMER (9501A only)
To change the On-Line period (factory default is 60 seconds), scroll through until you reach the feature as shown
below.
[1=Bck] [3=Fwd]
Do you want to edit
the On-Line Timer?
[*=Abort] [#=Yes]
Press # to access the feature. The display should appear...
-Program Options-
On-Line Timer
00 To 99 Sec. _ _ <----99 seconds max.
Please enter choice:
Enter the On-Line period. The next display should appear...
-Program Options-
* = Abort, # = Store
00 To 99 Sec. x x
Please enter choice:
Press * to abort or # to store entry. To quit, enter *000 while at PROGRAM MODE menu to return to NORMAL
MODE.
MULTIPLE / SINGLE ENTRANCE SELECT (9501A only)
To select Multiple or Single entrance (factory default is single entrance), scroll through until you reach the feature
as shown below.
[1=Bck] [3=Fwd]
Do you want to edit
Single/Multi option?
[*=Abort] [#=Yes]