Config.
--------------- P10.53
Unit gas type:
R410A
Parameter for setting the type of gas used in direct expansion circuits
[R410A – R32].
Visible only on units with at least one direct expansion circuit.
Config.
--------------- P10.16
Diff. pressure probe
lower limit: 0000Pa
--------------- P10.17
Diff. pressure probe
upper limit: 0100Pa
Parameters for setting the Start scale value of the differential pressure
transducer.
Parameters for setting the End scale value of the differential pressure
transducer.
Visible only on units with deltap or air flow rate control.
Config.
--------------- P10.29
LP pressure probe
presence on main
board: Y
Parameter for setting the presence of the low pressure transducer on
the base board.
Config.
--------------- P10.52
LP Probe Type:
0-5Vrat
Parameter for setting the type of low pressure transducer (0:0-5Vrat,
1:4-20mA).
Visible only with the low pressure transducer on base board enabled.
Config.
--------------- P10.30
LP pressure probe
lower limit: 00.0bar
--------------- P10.31
LP pressure probe
upper limit: 30.0bar
Start scale value of low pressure transducer.
End scale value of low pressure transducer.
Visible only on units with low pressure transducer on base board.
Config.
--------------- P10.20
Outdoor temperature
probe enable: N
External T probe enable.
Visible only on units without Direct Free Cooling.
Config.
--------------- P10.22
Brand:
Evolution+
Initial logo.
[Evolution+ | De' Longhi | ICS | Neutral | EATON | Mitsubishi RC ].
Config.
------------ P10.26-28
Unit serial number:
032000000
Setting of the unit serial number.