2.5.12 [P22] Settings 2 Menu
Accessible from: “Service” group.
Access mask to “Settings2” menu.
Settings
--------------- P29.01
Very High temperature
alarm setpoint: 10°C
Hazardous high temperature alarm setpoint.
2.5.13 [P23] Fan Menu
Accessible from: “Service” group.
Access mask to the “Fan” menu.
Fan
--------------- P23.01
Fan nominal speed:
070%
Parameter for setting the nominal speed of the internal fan.
Visible only on units with EC fans controlled by an analog signal.
Fan
--------------- P23.01
Fan nominal speed:
070%
Fan1:0000 Fan2:0000
Fan3:0000 Fan4:0000
Parameter for setting the nominal speed of the internal fan.
Visible only on units with EC fans controlled via serial communication.
Fan
--------------- P23.02
Fan economy function
enable: N
--------------- P23.03
Fan speed while in
economy mode: 50%
Enable the internal fan Economy Mode function.
Internal fan speed with Economy Mode function enabled.
Fan
--------------- P23.73
Missing Air Flow alarm
on ID2 enable: Y
Parameter for enabling the control of no air flow from the pressure switch.