2.6.2 Service Group
Par.N.
Description
Default
U.M.
Min.
Max.
20.01
Regulation probe configuration (0:Return – 1:Delivery)
0
-
0
1
20.02
Fan start delay after power on
0
s
0
999
20.03
Ventilation modulation start delay
120
s
0
500
20.04
Start regulation delay
60
s
20
999
20.05
Integral adjustment time (units without inverter)
900
s
0
999
20.08
Dirty filter sensor configuration (0:Disabled – 1:Enabled)
0
-
0
1
20.09
Smoke sensor configuration (0:Disabled – 1:Enabled)
0
-
0
1
20.10
Flooding sensor configuration (0:Disabled – 1:Enabled)
0
-
0
1
20.13
Remote ON/OFF contact configuration (0:Disabled – 1:Enabled)
0
-
0
1
20.18
Cold adjustment band
1.5
°C
0.5
20
20.19
Hot adjustment band
1.5
°C
0.5
20
20.20
Dehumidification adjustment band
5
%RH
1
15
20.21
Humidification adjustment band
5
%RH
1
15
20.22
Humidification adjustment integral time (PID)
900
s
0
999
20.23
Humidification adjustment derivative time (PID)
0
s
0
999
20.24
Cold setpoint minimum limit
18
°C
2
30
20.25
Cold setpoint maximum limit
32
°C
25
60
20.26
Hot setpoint minimum limit
12
°C
5
30
20.28
Delivery limit temperature configuration (0:Disabled – 1:Enabled)
0
-
0
1
20.29
Delivery air temperature minimum limit
10
°C
0
25
20.44
Frost-free function configuration (0:Disabled – 1:From LP transducer –
2:From delivery temperature – 3:From inlet gas temperature – 4:Cumulative)
0
-
0
4
20.47
Low pressure set point for frost-free function
7.5
bar
6
P
99.25
20.48
Low differential pressure for frost-free function
1
bar
0.5
9.9
20.49
Frost-free function activation delay
10
min
1
99
20.50
Configuration and activation of the counting of number of interventions per
hour count for the frost-free function (0:Disabled – 1:Enabled)
1
-
0
1
20.51
Number of interventions per hour for the frost-free function
3
-
1
5
20.53
Differential of Neutral Zone for switching on resources for control with air
delivery probe
1.5
°C
0.1
9.9
20.54
Differential of Neutral Zone for switching off resources for control with air
delivery probe
1.5
°C
0.1
9.9
20.98
Maximum variation of the switch-on Neutral Zone
3
°C
0
99.9
20.99
Maximum variation of the switch-off Neutral Zone
3
°C
0
99.9
20.55
Maximum delay for reducing extension of Neutral Zone for control with air
delivery probe
5
min
1
99
20.64
Position of FC valve for shutdown of resources
80
%
0
99
20.56
Minimum limit of cold setpoint for delivery air temperature control
10
°C
5
P
20.57
20.57
Maximum limit of cold setpoint for delivery air temperature control
25
°C
P
20.56
40
20.71
T&H limits alarm configuration with unit OFF (0: Disabled - 1: Enabled)
1
-
0
1