99
Version 38
Par.N.
Description
Default
U.M.
Min.
Max.
20.72
T&H limits alarm delay when unit ON
600
s
1
999
20.73
Safety Reduction Load LP function configuration (0:Disabled – 1:Enabled)
0
-
0
1
20.74
Circuit 1 Safety Reduction Load LP function activation setpoint
7.5
bar
5
9
20.75
Circuit 1 Safety Reduction Load LP function differential
1
bar
0
1
20.76
Step time for Circuit 1 Safety Reduction Load LP function
5
min
1
99
20.82
Auxiliary humidity probe address 129 configuration (0:Disabled – 1:Enabled)
0
-
0
4
20.83
Configuration of the ventilation control function (special function
02)(0:Disabled – 1:Return T. – 2:Delivery T. – 3:Temperature Delta)
0
-
0
3
20.84
Differential for control of special fan function 02
3
°C
0.1
9.9
20.94
Enable management of external fire control unit (0:Disabled – 1:Enabled)
0
-
0
1
21.21
Value of the cold ramp for maximum Free Cooling opening
50
%
0
100
21.09
Free Cooling damper adjustment configuration (0:Disabled – 1:Enabled)
0
-
0
1
21.10
Free Cooling damper control type configuration (0:Digital – 1:Modulating)
0
-
0
1
21.11
Setpoint (T_ROOM-T_EXTERNAL) for Free Cooling damper adjustment
3
°C
0
50
21.12
Free Cooling damper adjustment band
1
°C
0
9.9
21.13
Minimum Free Cooling damper opening
0
%
0
100
21.14
Maximum Free Cooling damper opening
100
%
P
21.13
100
21.32
Configuration of simultaneous operation of Direct Free Cooling and
compressor or 3-way valve
0
-
0
1
21.33
Direct Free Cooling activation delay after compressor shutdown/closing of
the water valves
180
s
0
9999
21.15
Free Cooling management configuration for high humidity
0
-
0
1
21.16
Humidity limit for Free Cooling damper disable
60
%RH
0
99.9
21.17
Humidity band to disable Free Cooling damper
1
%RH
0
9.9
21.18
Free Cooling damper adjustment configuration with compressor alarm
(0:Disabled – 1:Enabled)
0
-
0
1
21.19
Setpoint (T_ROOM-T_EXTERNAL) to regulate the Free Cooling damper
with compressor alarm
1
°C
1
50
21.20
Free Cooling damper adjustment band with compressor alarm
0.5
°C
0
9.9
21.26
Enable washing mode (0:Disabled - 1:Enabled)
0
-
0
1
22.01
Low temperature alarm setpoint
10
°C
0
30
22.02
High temperature alarm setpoint
32
°C
20
50
22.03
Low humidity alarm setpoint
30
%RH
0
70
22.04
High humidity alarm setpoint
80
%RH
30
99
22.17
Step 1 heater operating hours for maintenance setpoint (Thousands)
0
h
0
99
22.18
Step 2 heater operating hours for maintenance setpoint (Thousands)
0
h
0
99
22.19
Humidifier operating hours for maintenance setpoint (Thousands)
0
h
0
4
22.20
Modulating heating element operating hours for maintenance setpoint
(Thousands)
0
h
0
99
22.21
Alarm reset by supervision system (0:Disabled – 1:Enabled)
0
-
0
1
22.29
Configuration of presence of KIPlink module (0:Disabled – 1:Enabled)
0
-
0
1