2.5.8 [P--] Default Menu
Accessible from: “Factory” group.
Access mask to the “Default” menu (initialisation of the factory parameters).
This restores the default values.
Wipes the memory and restores the default values of the parameters. The chiller
must then be programmed with the parameter set during factory testing.
The mask is not displayed when the chiller is ON.
Default
Reset History
of Alarms
N
Deletes the contents of the alarms log on the display.
Default
Connect KIPlink to the
WiFi network
CLIMA_WIFIeea N
Verify the IP achieved
with specific wizard
tool
It allows to start the test mode for the KIPlink.
2.5.9 [P20] Regulations Menu
Accessible from: “Service” group.
Access mask to “Regulations” menu.
Regulations
--------------- P20.01
Regulation probe
choice: Return Temp
Type of temperature probe used for adjustment.
[Return | Delivery].
Visible only on chilled water units or direct expansion units with at least one
inverter compressor.
Regulations
--------------- P20.02
Fan start delay after
power-ON: 000s
Fan start delay after power ON.