Setpoint
--------------- P50.07
Dehumdific. Setpoint
with LAN limits: 75%RH
--------------- P50.08
Humdific. Setpoint
with LAN limits: 35%RH
Dehumidification setpoint during LAN out of range.
Humidification setpoint during LAN out of range.
Setpoint
--------------- P50.09
Min return temperature
for dehumid OFF:18.0°C
Parameter for minimum room temperature and dehumidifier off.
Visible only on units with at least one direct expansion circuit on which the
dehumidification function is enabled.
Setpoint
--------------- P50.14
Temp. setpoint for
fan regulation with
fan reg. funct.
enabled: 24.0°C
Temperature setpoint for fan control.
Setpoint
--------------- P50.15
Treturn setpoint for
fan regulation with
return temp. fan reg.
funct. Enabled
with LAN limits:30.0°C
Return temperature setpoint for adjustment of the fan based on the return
temperature during LAN out of range.
2.5.26 [P900] Clock Menu
Accessible from: “Main” group.
Access mask to “Clock” menu.
Clock
Clock card
not installed
Mask indicating the lack or damage to the clock board.
Clock
Clock Config.
Date Time
22/11/18 13:58
Current date and time setting.
Clock
Time bands
not enabled.
See Scheduler menu
Indicates that the time bands have been set correctly, though they are not enabled.
To enable them, go to the "Scheduler" menu of the "User" group.