2.5.19 [P28] Regulations 2 Menu
Accessible from: “Service” group.
Access mask to “Regulations 2” menu.
Regulations 2
No Regulations 2
Parameters Available
Mask displayed when none of the parameters of this menu for the unit are
available.
Regulations 2
--------------- P28.18
Sup. Probes regulation
TH NTC1---------------
THr1 THr2 THr3 THr4
Param. Value: 00511
Parameter for indicating the temperature probes that will be used for the
calculation of the delivery air temperature.
Bit 0: NTC1 – Bit 1: TH -
Bit 5: THr1 – Bit 6: THr2 – Bit 7: THr3 – Bit 8: THr4
Regulations 2
--------------- P28.19
TH NTC1 --------------
THr1 THr2 THr3 THr4
Param. Value: 00511
Parameter for indicating the temperature probes that will be used for the
calculation of the return air temperature.
Bit 0: NTC1 – Bit 1: TH -
Bit 5: THr1 – Bit 6: THr2 – Bit 7: THr3 – Bit 8: THr4
Regulations 2
--------------- P28.20
Ret. Calculation type:
1
st
probe enabled
--------------- P28.21
Sup. Calculation type:
1
st
probe enabled
Parameter for setting the type of calculation of the return air temperature.
Parameter for setting the type of calculation of the delivery air temperature.
Regulations 2
--------------- P28.22
UV Lamp Activation:
Disabled
-----------------------
-----
Parameter for choosing the type of UV lamp activation command.
[Disabled].
Parameter for switching the UV lamp on/off.
Visible only with UV lamp activation from keypad.
Regulations 2
--------------- P28.30
Measurement system:
International
Imperial system enable [0: International metric system - 1: Imperial metric
system].