78
Version 38
Mask of the terminal
Description
Par.N.
Optional
--------------- P27.24
Maximum compensation
of cooling set: 02.0°C
Parameter for setting the maximum setpoint offset cooling.
Visible only if the setpoint compensation function is enabled.
27.24
Optional
--------------- P27.25
Temp. for Min compens.
of heating set: 24.0°C
--------------- P27.26
Temp. for Max compens.
of heating set: 28.0°C
Parameter for setting the start point of heating setpoint compensation.
Parameter for setting the end point of heating setpoint compensation.
Visible only if the signal type is set to REM T/H setpoint compensation and the
heating resources are present.
27.25
27.26
Optional
--------------- P27.27
Maximum compensation
of heating set: 02.0°C
Parameter for setting the maximum setpoint offset heating.
Visible only if the setpoint compensation function is enabled and heating resources
are present.
27.27
Optional
--------------- P27.33
T+H external probe
(humidity sensor): N
--------------- P27.34
T+H Supply probe
(humidity sensor): N
Parameter for enabling the external serial T/H probe.
Parameter for enabling the air delivery serial T/H probe.
27.33
27.34