Optional
--------------- P27.29
Diff. between setpoint
humidification and
dehumidification: 05%
Parameter for setting the minimum difference between humidification setpoint and
dehumidification setpoint.
Visible only if both the humidifier and the dehumidification function are enabled.
Optional
--------------- P27.11
Damper enable:
N
--------------- P27.12
Damper opening time:
120sec
Enable the delivery air damper.
Opening stroke time for the damper.
Optional
--------------- P27.13
Energy Analyzer 1
enable: N
Enable the network analyser.
Optional – Enrg. Anlz.
--------------- P27.14
System type:
3-phase unbal ¾-wire
--------------- P27.15
Transformer ratio:
00020
Type of power supply system.
It can be a 1-2-3 phase power supply system with balanced or unbalanced load and
with or without neutral.
Input current transformation ratio.
Visible only if the network analyser is enabled.
Optional
--------------- P27.30
Energy Analyzer 2
enable: N
Parameter for enabling the management of the network transducer 2 (N:disabled -
Y:enabled).
Optional- Enrg. Anlz.2
--------------- P27.31
System type:
3-phase unbal ¾-wire
--------------- P27.32
Transformer ratio:
00020
Parameter for configuring the power supply system that can be 1-2-3 phases with
balanced/unbalanced load, with or without neutral (Default: system 3/4 unbalanced
wires) and Parameter for configuring the supply current transformer ratio. (Default:
20):
Optional
--------------- P27.20
Setpoint Compensation
enable: N
--------------- P27.21
Type of signal for
compensation: 0-1V
Setpoint offset function enable.
Setpoint offset signal type.
[0-1V
DC
| 0-5 V
DC
| 0.5-4.5V
DC
| 0-20mA | 4-20mA | T+H Remote | External T+H (not
available)].
Optional
--------------- P27.22
Temp. for Min compens.
of cooling set: 24.0°C
--------------- P27.23
Temp. for Max compens.
of cooling set: 28.0°C
Parameter for setting the start point of cooling setpoint compensation.
Parameter for setting the end point of cooling setpoint compensation.
Visible only if the type of signal for the compensation of the setpoint is set to REM
T/H.