2.5.17 [P--] Manual Menu
Accessible from: “Service” group
Access mask to “Manual” menu.
This menu contains the masks for the manual control of the unit.
This menu is used to reset the network analyser counts and reset the operating
hours and the start counts of the various unit components.
Manual
----------------------
Manual operation
enabling: N
----------------------
Internal fan
manual activation: N
Enable manual operation.
Enable manual operation of internal fan (unit in operation).
Manual
----------------------
Humidity / Temperature
manual setting enabl:N
----------------------
Room temperature value
manual setting: 24.0°C
Enable the manual setting of air temperature and humidity.
Manual return air temperature value.
Visible only if manual setting of air temperature and humidity is enabled.
Manual
----------------------
Ambient humidity
simulated val.:50.0%RH
Manual return air humidity value.
Visible only if manual setting of air temperature and humidity is enabled.
Manual
----------------------
Heaters step 1
manual activation: N
----------------------
Heaters step 2
manual activation: N
Manual request to switch on first stage heaters.
Manual request to switch on second stage heaters.
Visible only if on/off type electrical heaters are present, if manual operation is
enabled and the unit is running.
Manual
----------------------
Digital FC damper
manual activation: N
----------------------
Analog FC damper
manual opening: 000%
Manual request to open Direct Free Cooling damper.
Direct Free Cooling damper opening manual request value.
Visible only if the direct Free Cooling damper is present, if manual operation is
enabled and the unit is running.
Manual
----------------------
Internal Humidifier
>not active
----------------------
Humidifier
manual activation: N
Display operation of the internal humidifier.
Manual request for internal humidifier activation.
Visible only if an internal type humidifier is present, if manual operation is enabled
and the unit is running.
Manual
----------------------
Start pre-cleaning: N
>not active
----------------------
Manual Drain: N
Manual request for internal humidifier pre-wash.
Visible if there is not already a humidifier pre-wash manual request.
Display operation of the internal humidifier.
Manual request for internal humidifier discharge.
Visible only if there is a manual internal humidifier activation, if manual operation is
enabled and the unit is running.