2.5.7 [P15] Safety 2 Menu
Accessible from: “Factory” group.
Mask of the terminal
Description
Par.N.
Safety 2
Access mask to “Safety 2” menu.
Safety 2
--------------- P15.13
Low return temperature
dehum. Limit: Band+Lim
Parameter for setting the type of inhibition of the dehumidification due to
low return temperatures.
[Band and limit |Limit only].
Visible only on direct expansion units with dehumidification function
enabled.
15.13
Safety 2
--------------- P15.15
Periodic Check funct.
Enable: Y
--------------- P15.16
Periodic Check funct.
Period: IIImin
Periodic Check function enable.
Periodic Check function running interval.
Visible in case of s-MEXT unit.
15.15
15.16
Safety 2
--------------- P15.17
Periodic Check funct.
Reduction: Iistep
--------------- P15.18
Periodic Check funct.
Duration: IIImin
Periodic Check function step reduction.
Periodic Check function duration.
Visible in case of s-MEXT unit.
15.17
15.18