2.5.20 [P30] Serial Menu
Accessible from: “User” group.
Access mask to “Serial” menu (Serial connections).
Serial
--------------- P30.01
BMS supervision
enable: N
Enable the BMS supervisor.
Serial
--------------- P30.02
BMS1 address:
011
--------------- P30.03
BMS1 protocol type:
Standard
BMS1 port address.
BMS1 port protocol type.
[Standard | Modbus | GSM Modem | LON | Bacnet | TCP/IP | WinLoad].
Visible only if supervision is enabled.
Serial
--------------- P30.04
BMS1 baudrate:
19200
Baud rate for BMS1 port communication.
[1200 | 2400 | 4800 | 9600 | 19200 | 38400].
Visible only if supervision is enabled.
Serial
--------------- P30.05
ON/OFF by BMS enable:
N
Serial
--------------- P30.12
BMS2 supervision
enable: N
Parameter for the configuration of the supervision presence on port BMS2.
Visible only if supervision is enabled and KIPlink is not.
Serial
--------------- P30.13
BMS2 address:
002
--------------- P30.14
BMS2 baudrate:
38400
BMS2 port address.
Baud rate for BMS2 port communication.
[1200 | 2400 | 4800 | 9600 | 19200 | 38400]
Visible only if supervision is enabled on both ports and KIPlink is not enabled.
Serial
--------------- P30.09
Temp. regulation from
Supervisor enable: N
Enabling adjustment according to temperature provided by BMS.