89
Version 38
Mask of the terminal
Description
Par.N.
Alarm out addressing 2
--------------- P33.76
(543) Supply Humid.
above max limit: A
--------------- P33.77
(542) Supply Humid.
below min limit: A
Addressing of the delivery humidity above maximum limit alarm on digital output.
Addressing of the delivery humidity below minimum limit alarm on digital output.
Visible only if the delivery air T/H probe is present.
33.76
33.77
Alarm out addressing 2
--------------- P33.80
(307) T+H sup. Offline
alarm on output: A
Addressing of the delivery serial probe offline alarm on digital output.
Visible only if the delivery air T/H probe is present.
33.80
Alarm out addressing 2
--------------- P33.81
(308) T+H sup. Temper.
alarm on output: A
--------------- P33.82
(309) T+H sup. Humid.
alarm on output: A
Alarm out addressing 2
Addressing of the delivery temperature serial probe alarm on digital output.
Addressing of the delivery humidity serial probe alarm on digital output.
Visible only if the delivery air T/H probe is present.
33.81
33.82
Alarm out addressing 2
---------------P33.83
(840)Mr.SLIMMSystem
alarmonoutput:A
---------------P33.84
(841)Mr.SLIMMCirc.
alarmonoutput:A
Addressing of PAC–IF Client system alarm (0:A – 1:None – 2:B)
Addressing of PAC–IF Client circuit alarm (0:A – 1:None – 2:B)
33.83
33.84
Alarm out addressing 2
---------------P33.85
(842)Mr.SLIMMProbes
alarmonoutput:A
---------------P33.86
(843)Mr.SLIMS1System
alarmonoutput:A
Addressing of PAC–IF Client proble alarm (0:A – 1:None – 2:B)
Addressing of PAC–IF Server 1 system alarm (0:A – 1:None – 2:B)
33.85
33.86
Alarm out addressing 2
---------------P33.87
(844)Mr.SLIMS1Circ.
alarmonoutput:A
---------------P33.88
(845)Mr.SLIMS1Probes
alarmonoutput:A
Addressing of PAC–IF Server 1 circuit alarm (0:A – 1:None – 2:B)
Addressing of PAC–IF Server 1 probe alarm (0:A – 1:None – 2:B)
33.87
33.88
Alarm out addressing 2
---------------P33.89
(188)Mr.SLIMMOffline
alarmonoutput:A
---------------P33.90
(189)Mr.SLIMS1Offlin
alarmonoutput:A
Addressing of PAC–IF Client offline alarm (0:A – 1:None – 2:B)
Addressing of PAC–IF Server 1 offline alarm (0:A – 1:None – 2:B)
33.89
33.90