928
APPX
Appendix 9 Processing Time
D2 is determined as follows.
*2 The size of the devices/labels to be transferred (tracked) can be checked by clicking the [Size Calculation] button in "Detailed Setting" of
"Device/Label Detailed Setting". ( Page 462 Detailed setting)
*3 Even though global labels/local labels are deleted by the online change, the size of the tracking data of the global labels/local labels are
the same as the one before the online change. The size is updated when the program and global label setting file to which all data is
rebuilt (reassigned) are written to the programmable controller and the operating status of the CPU module is switched from STOP to
RUN.
*4 This indicates the number of programs where local devices are set to use in the "Setting of Device/File Use Or Not" window of the
program setting of the CPU parameter.
D4 is determined as follows.
*5 When calculating D7, use this value for "System data (safety)".
*6 Since the maximum number of mountable CC-Link IE Field Network module is 8, the maximum number of connections that can be set in
the safety communication setting is 960 (120 connections 8 modules).
D5 is determined as follows.
*7 The size of the devices/labels to be transferred (tracked) can be checked by clicking the [Size Calculation] button in "Detailed Setting" of
"Device/Label Detailed Setting". ( Page 462 Detailed setting)
*8 Even though global labels/local labels are deleted by the online change, the size of the tracking data of the global labels/local labels are
the same as the one before the online change. The size is updated when the program and global label setting file to which all data is
rebuilt (reassigned) are written to the programmable controller and the operating status of the CPU module is switched from STOP to
RUN.
*9 This indicates the number of programs where local devices are set to use in the "Setting of Device/File Use Or Not" window of the
program setting of the CPU parameter.
Item Size
*2
Global device (other than the refresh data
register (RD))
Follows the tracking transfer settings. ( Page 460 Tracking transfer setting)
Local device Total size of local devices of the device/label memory area detailed setting the number of programs on the
program setting
*4
Global label
*3
Follows the global label settings.
Local label
*3
Follow the local label settings.
Item Size
System data Fixed data
7602
PID control instruction information
782 (0 (when not used))
Data that varies depending on the tracking device/label setting
16 (No. of tracking settings of T, ST, C, and LC) + 8 (No. of global device tracking settings of other
devices)
Variable depending on safety communication status
*5
136 + (29 (Number of connections set in the safety communication setting of all the modules
*6
)
Signal flow memory (standard/safety) (Total number of steps of control system execution programs, or total number of steps of rising/falling
instruction in an FB)/16
(The digit after the decimal point is round up.)
Refresh data register (RD) Follows the tracking transfer settings. ( Page 628 Tracking transfer setting)
Item Size
*7
Global device (standard) (other than the refresh
data register (RD))
Follows the tracking transfer settings. ( Page 628 Tracking transfer setting)
Global device (safety) Follows the safety device/label area in the device/label memory settings.
Local device (standard/safety) Total size of local devices of the device/label memory area detailed setting the number of programs on the
program setting
*9
Global label (standard)
*8
Follows the global label settings.
Global label (safety)
*8
Follows the safety global label settings.
Local label (standard)
*8
Follows the local label settings of each standard program.
Local label (safety)
*8
Follows the local label settings of each safety program.
Standard/safety shared label Follows the standard/safety shared label setting file.

Table of Contents

Related product manuals